Description
Pepperl+Fuchs Intrinsic Safety & Zener Barriers
01. Product Overview
Pepperl+Fuchs intrinsic safety and Zener barriers are designed to protect electrical circuits and interface field instrumentation operating in potentially explosive industrial environments.
These devices are installed between hazardous-area field equipment and safe-area control systems to limit electrical energy, provide signal isolation, and maintain the required intrinsic safety protection for compatible field circuits.
The product portfolio includes three major technology platforms:
Z-System – Zener Barriers
Zener barriers use Zener diodes, current-limiting resistors, and protective fuses to restrict the electrical energy transferred from safe areas into hazardous areas. They require a dedicated, reliable grounding connection to maintain their intrinsic safety function.
K-System – DIN-Rail Isolated Barriers
K-System isolated barriers provide galvanic isolation between field circuits and control systems. They are designed for DIN-rail mounting and offer flexible configurations for analog signals, digital signals, NAMUR sensors, temperature measurement, and process control.
Selected K-System modules use the Power Rail system to simplify power distribution and reduce wiring requirements.
H-System – Termination-Board Mounted Isolated Barriers
H-System modules are designed for installation on dedicated termination boards. They provide compact, high-density signal interfacing for distributed control systems (DCS) and safety instrumented systems (SIS).
Major product families include Z-System, KFD2, KCD2, KFD0, HiC, and associated Power Rail and termination board accessories.
These products are widely used in oil and gas, petrochemical processing, chemical plants, pharmaceutical production, and other hazardous-area process industries.
02. Product Features
- Intrinsic Safety Protection: Limits electrical energy transferred into hazardous-area field circuits to prevent ignition under specified fault conditions.
- Galvanic Isolation: Selected isolated barriers provide electrical separation between field circuits, control systems, and power supplies.
- Multiple Signal Types: Supports analog input/output, digital input/output, NAMUR sensors, temperature signals, and frequency conversion.
- Zener Barrier Technology: Z-System modules use Zener diodes, current-limiting resistors, and fuses to restrict energy transfer.
- Flexible Installation: Zener barriers and K-System modules are available for 35 mm DIN-rail mounting.
- Power Rail Integration: Selected K-System modules support centralized power distribution through the Power Rail system.
- DCS & SIS Compatibility: H-System and selected K-System products support integration with industrial control and safety systems.
- HART Compatibility: Selected isolated barriers provide transparent HART communication for smart field instruments.
- Multiple Channel Configurations: Available single-channel, dual-channel, and other application-specific configurations.
- Functional Safety: Selected models are certified for SIL 2 or SIL 3 applications according to their individual safety documentation.
- International Approvals: Selected models carry ATEX, IECEx, FM, cULus, and other hazardous-area approvals.
- Compact Modular Design: Narrow housings and termination-board solutions help optimize control cabinet space.
- Industrial Reliability: Designed for continuous operation in demanding process automation environments.
03. Available Product Series
Pepperl+Fuchs intrinsic safety barriers are organized into the following major product families.
A. Z-System – Zener Barriers
Z-System provides passive Zener barrier solutions for different intrinsic safety circuit requirements.
Zener Barrier Series
- Z7 Series – DC Zener barriers with positive polarity.
- Z8 Series – DC Zener barriers with negative polarity.
- Z9 Series – AC Zener barriers for alternating and direct voltage signals.
- Z***.F Variants – Configurations with replaceable backup fuses.
- Z***.CL Variants – Configurations with current-limited field circuits.
- Z***.H Variants – High-power Zener barrier configurations.
- Z***.R Variants – Asymmetrical Zener barrier configurations.
Available models include different voltage limits, current ratings, channel counts, polarity configurations, and intrinsic safety parameters.
B. K-System – DIN-Rail Isolated Barriers
K-System is one of Pepperl+Fuchs’ major process interface product platforms.
Analog Input & Transmitter Power Supplies
- KFD2-STC Series – SMART transmitter power supplies and isolated analog input interfaces.
- KFD2-SCD Series – SMART current driver and signal conditioning modules.
- KFD2-SCS Series – SMART transmitter and valve positioner interface solutions.
Digital Input & Switch Amplifiers
- KFD2-SR Series – Switch amplifiers for NAMUR sensors and dry contacts.
- KFD2-SR2 Series – Single-channel and dual-channel isolated switch amplifiers.
- KFD2-SH Series – Specialized switch amplifier configurations.
Analog & Digital Signal Interfaces
- KCD2 Series – Compact isolated barrier and signal conditioning modules.
- KFD0 Series – Specialized interface and isolated barrier solutions.
- KFD2-UT Series – Temperature and universal signal interface modules.
Power Distribution
- Power Rail – DIN-rail power distribution system for compatible K-System modules.
- KFD2-EB2 Series – Power feed and distribution accessories.
C. H-System – Termination-Board Mounted Isolated Barriers
H-System provides isolated barrier modules for high-density control system installations.
HiC Series
- HiC2025 – SMART transmitter power supply.
- HiC2025A – SMART transmitter power supply variants.
- HiC2031 – Process interface and isolated barrier modules.
- HiC2422 – SMART transmitter power supply and current driver for valve positioner control and monitoring.
- Additional HiC modules – Analog, digital, temperature, and specialized process signal interfaces.
H-System Accessories
- H-System Termination Boards – Dedicated mounting and connection platforms.
- HiCTB Series – Termination boards for compatible DCS and SIS installations.
- H-System Power and Connection Accessories – Components for system integration.
D. Safety System & DCS Integration Solutions
Pepperl+Fuchs also offers application-specific isolated barrier platforms for major control system manufacturers.
- Emerson DeltaV – K-System and H-System interface solutions.
- Schneider Electric Triconex – H-System and K-System barrier platforms.
- Yokogawa CENTUM VP – H-System interface and termination board solutions.
- Yokogawa ProSafe-RS – Safety-related isolated barrier and termination board solutions.
- Foxboro DCS – Customized H-System interface platforms.
Actual module compatibility depends on the selected controller, I/O card, termination board, and system configuration.
04. Available Models & Technical Specifications
Z864 – Zener Barrier
- Product Type: Zener Barrier
- Series: Z-System
- Channel Configuration: 2-Channel
- Circuit Type: DC
- Polarity: Negative
- Working Voltage: 10 V at 10 µA
- Nominal Resistance: 1000 Ω
- Series Resistance: Maximum 1033 Ω
- Fuse Rating: 50 mA
- Hazardous-Area Connection: Terminals 1, 2 and 3, 4
- Safe-Area Connection: Terminals 5, 6 and 7, 8
- Mounting: 35 mm DIN Rail
- Connection: Screw Terminals
- Protection Rating: IP20
- Operating Temperature: -20 to +60 °C
- Dimensions: 12.5 × 115 × 116 mm (W × H × D)
- Weight: Approximately 150 g
- Hazardous-Area Approval: ATEX and IECEx configurations, subject to certificate conditions
KFD2-STC4-Ex1 – SMART Transmitter Power Supply
- Product Type: SMART Transmitter Power Supply
- Series: K-System
- Signal Type: Analog Input
- Channel Configuration: 1-Channel
- Hazardous-Area Input: 0/4–20 mA
- Output Signal: 0/4–20 mA
- Rated Supply Voltage: 20–35 V DC
- Power Consumption: Approximately 1.9 W
- Input Resistance: Model-dependent terminal configuration
- Output Load: 0–800 Ω
- Output Ripple: ≤ 50 µA RMS
- Communication: HART-compatible signal transmission
- Mounting: DIN Rail
- Power Supply: Power Rail or terminals
- Functional Safety: Up to SIL 2 for the relevant certified configuration
KFD2-SR2-Ex2.W – Two-Channel Switch Amplifier
- Product Type: Switch Amplifier / Isolated Barrier
- Series: K-System
- Channel Configuration: 2-Channel
- Input: NAMUR Sensors or Dry Contacts
- Output: Relay Contacts
- Power Supply: 24 V DC through Power Rail or terminals
- Function: Reversible operating mode
- Line Fault Detection: Available
- Mounting: DIN Rail
- Interface: Galvanically isolated signal interface
- Functional Safety: Up to SIL 2 (SC 3) according to IEC/EN 61508
- Application: Hazardous-area digital signal monitoring
HiC2025 – SMART Transmitter Power Supply
- Product Type: SMART Transmitter Power Supply
- Series: H-System
- Signal Type: Analog Input
- Channel Configuration: 1-Channel
- Power Supply: 24 V DC through compatible system power arrangement
- Input: Two-Wire SMART Transmitters or Current Sources
- Output: 4–20 mA or 1–5 V, depending on configuration
- Isolation: Galvanic isolation
- Mounting: Compatible H-System Termination Board
- Functional Safety: SIL 2 (SC 3), according to the applicable product documentation
- Application: Process instrumentation and DCS integration
The technical specifications above refer to representative individual models. Verify complete ordering codes, electrical parameters, safety approvals, and compatible termination boards before selecting or replacing a module.
05. Industrial & Mobile Applications
Pepperl+Fuchs intrinsic safety and Zener barriers are widely used in hazardous-area process automation and industrial control systems.
Oil & Gas Industry
- Pressure transmitter signal interfacing
- Flow meter signal isolation
- Tank level monitoring
- Gas detection system interfaces
- Hazardous-area valve positioner control
- Offshore process instrumentation
Chemical & Petrochemical Processing
- Chemical reactor instrumentation
- Temperature transmitter interfaces
- Pressure and flow signal conditioning
- Hazardous-area sensor connections
- Process control system integration
- Explosion-protected measurement circuits
Pharmaceutical & Food Processing
- Process temperature monitoring
- Tank level measurement
- Pressure transmitter integration
- Hazardous-area equipment interfaces
- Hygienic process instrumentation
Power Generation & Energy
- Boiler instrumentation
- Turbine monitoring interfaces
- Fuel system measurement
- Gas monitoring and process control
- Safety instrumented system integration
Industrial Process Automation
- PLC and DCS signal interfacing
- Analog and digital signal isolation
- NAMUR sensor signal processing
- Relay output control
- SMART transmitter communication
- Safety-related instrumentation
Hazardous-Area Control Cabinets
- DIN-rail isolated barrier installation
- Zener barrier circuit protection
- H-System termination board integration
- Control cabinet signal distribution
- Intrinsic safety loop protection
06. More Models & Technical Specifications
Additional Pepperl+Fuchs intrinsic safety interface products include:
Z-System
- Z7 Series – Positive-polarity DC Zener barriers.
- Z8 Series – Negative-polarity DC Zener barriers.
- Z9 Series – AC Zener barriers.
- Z864 – Two-channel DC Zener barrier, negative polarity.
- Z964 – Two-channel AC Zener barrier.
- Replaceable-fuse and specialized current-limiting variants.
K-System
- KFD2-STC Series – SMART transmitter power supplies.
- KFD2-SR Series – NAMUR switch amplifiers.
- KFD2-SCD Series – Signal conditioning and current driver modules.
- KCD2 Series – Compact isolated barriers and interface modules.
- KFD0 Series – Specialized signal interface modules.
- KFD2-UT Series – Temperature and universal signal interfaces.
- Power Rail – Compatible power distribution accessories.
H-System
- HiC2025 – SMART transmitter power supply.
- HiC2025A – Transmitter power supply variant.
- HiC2031 – Process interface module.
- HiC2422 – SMART transmitter power supply and current driver.
- HiCTB Series – H-System termination boards.
Available Technical Configurations
- Barrier Technology: Zener / Galvanically Isolated
- System Type: Z-System / K-System / H-System
- Signal Type: Analog / Digital / NAMUR / Temperature
- Input Signal Range
- Output Signal Range
- Working Voltage
- Maximum Input Voltage
- Current Limitation
- Series Resistance
- Channel Configuration
- Isolation Voltage
- Power Supply Voltage
- HART Communication Compatibility
- Relay / Transistor Outputs
- Line Fault Detection
- DIN-Rail Mounting
- Termination Board Compatibility
- Power Rail Compatibility
- Hazardous-Area Classification
- ATEX / IECEx / FM / cULus Approvals
- SIL Classification
- Operating Temperature
- Housing Dimensions
Technical specifications and safety approvals are model-specific. Always check the official product datasheet and intrinsic safety certificate for the complete ordering code and intended hazardous-area application.
Looking for additional Pepperl+Fuchs isolated barriers, Zener barriers, or replacement interface modules? Contact our online customer service team for model identification and sourcing assistance.